Inspection
Inspection Details
Equipment ID
16075
16075
Inspection Date
1/31/2022
1/31/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
3abb92a1-22f6-4465-aa55-8ae5307e4e79
3abb92a1-22f6-4465-aa55-8ae5307e4e79
Location
St Louis Properties LLC
3822 Westminster Pl, St. Louis, MO
Phone: (314) 561-6400
3822 Westminster Pl, St. Louis, MO
Phone: (314) 561-6400
Owner
Attn: St. Louis Properties
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (918) 575-0716
Email: cm@coronadoplaceandtowers.com
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (918) 575-0716
Email: cm@coronadoplaceandtowers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean pit of water and debris. | 1/28/2020 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | No | No | Number the back of hoistway doors. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 1/31/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher needs to be serviced. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher needs to serviced | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned of water & debris. Place cover on sump pump. Re-inspection required | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV shall be tested with full load. Tagged & sealed after satisfactory test. Re-inspection required | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work, Re-inspection required | 2/17/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall not be stored in machine room. | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | Provide machine room ventilation to meet OEM temperature/humidity requirements. HVAC is not working. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | 4x4 electrical box in machine room needs to have wiring inside box and cover installed. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Cab lighting - All lamps shall work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing/damaged pickup rollers, 3rd floor. | |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | Hoistway doors shall be self-closing. 4th floor door jams. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Hoistway doors need to be numbered on hoistway side. Not all are numbered. | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump is missing cover. |