Inspection
Inspection Details
Equipment ID
23295
23295
Inspection Date
2/2/2022
2/2/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
28
28
External ID
c2290738-9184-4db1-a707-7cfff2043352
c2290738-9184-4db1-a707-7cfff2043352
Location
EVO Apartments
9015 EAGER RD, SAINT LOUIS, MO
Phone: (314) 627-1070
9015 EAGER RD, SAINT LOUIS, MO
Phone: (314) 627-1070
Owner
Attn: EVO
MV One LLC
33 W MONROE ST, CHICAGO, IL 60603
Phone: (314) 649-5003
Email: resi-evo-acctg@dklivingapts.com
MV One LLC
33 W MONROE ST, CHICAGO, IL 60603
Phone: (314) 649-5003
Email: resi-evo-acctg@dklivingapts.com
Billing
Attn: EVO Apartments
MV ONe LLC
9015 EAGER RD, SAINT LOUIS, MO 63144
Phone: (314) 649-5003
Email: resi-evo-acctg@dklivingapts.com
MV ONe LLC
9015 EAGER RD, SAINT LOUIS, MO 63144
Phone: (314) 649-5003
Email: resi-evo-acctg@dklivingapts.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery back-up system does not work. | 2/2/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Provide missing lobby car number on door buck. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current elevator operating certificate. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 6/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | Provide missing bottom door fire stop. | 6/19/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/27/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related equipment from the machine room | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | Yes | Drive machine brake is unable to hold 125% rated load. Repair or replace brake, Red-tagged, Re-inspection required | 2/24/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery backup system does not work, needs repaired. Re-inspection required | 2/24/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery backup system does not work, needs repaired. Re-inspection required | 3/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Existing battery backup system does not work, needs repaired. Re-inspection required | 4/28/2026 |