Inspection
Inspection Details
Equipment ID
15715
15715
Inspection Date
2/1/2022
2/1/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
na
na
Slide
Governor Rope Pull
Door Closing Force
na
na
External ID
0b7f2ec3-3701-4723-9228-39d9ef0589a0
0b7f2ec3-3701-4723-9228-39d9ef0589a0
Location
Convention Center
600 N 6th St, St. Louis, MO
Phone: (314) 982-1400
600 N 6th St, St. Louis, MO
Phone: (314) 982-1400
Owner
Attn: Metro Accounts Payable
Metro Accounts Payable
707 N 1st St, St. Louis, MO 63102
Phone: (314) 982-1400
Email: eastefano@MetroStLouis.org
Metro Accounts Payable
707 N 1st St, St. Louis, MO 63102
Phone: (314) 982-1400
Email: eastefano@MetroStLouis.org
Billing
Attn: Metro Accounts Payable
Metro Accounts Payable
PO Box 1349, St. Louis, MO 63188
Phone: (314) 982-1400 Ext: 2276
Email: ajghiassi@MetroStLouis.org
Metro Accounts Payable
PO Box 1349, St. Louis, MO 63188
Phone: (314) 982-1400 Ext: 2276
Email: ajghiassi@MetroStLouis.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 12/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell not working. | 12/18/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Cab ventilation not working. | 12/1/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated certificate in machine room. | 12/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site | 1/13/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Oil line fitting going into tank leaking oil onto floor needs repair | 1/13/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room can not be used for storage of non elevator equipment | 12/7/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | No | No | Replace leaking victaulic fitting on hydraulic line in the machine room. Fitting is on the bottom side of the shut off valve | 12/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Phone in the elevator cab does not work. Repair or replace | 2/1/2022 |
| A17.1-2016 : Elevators | 1.14 - Ventilation | 2.14.2.3 | Yes | No | Elevator cab ventilation fan does not work on auxiliary power (battery power) needs repaired. Re-inspection required | 10/4/2024 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Elevator cab door restrictor does not work, needs repaired. Re-inspection required | 10/4/2024 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Safety retainers are missing on top & bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/4/2024 |