Inspection
Inspection Details
Equipment ID
11771
11771
Inspection Date
7/12/2018
7/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
620
620
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
87e24be9-86e8-4046-beb0-a6e442905f75
87e24be9-86e8-4046-beb0-a6e442905f75
Location
Vashon High School
3035 CASS AVE, SAINT LOUIS, MO
3035 CASS AVE, SAINT LOUIS, MO
Owner
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101-1015
801 N 11TH ST, SAINT LOUIS, MO 63101-1015
Billing
Attn: Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601-0423
PO BOX 423, CHILLICOTHE, MO 64601-0423
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace the missing cab ceiling panel. Cab lighting shall be covered. | 9/9/2019 |
| conversion | conversion | n/a | No | No | Emergency light is not operational. | 9/9/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The emergency light shall be operational. | 9/9/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency bell shall be operational with 110v source removed. | 9/9/2019 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Elevator appears to have a sync issue with jacks (twin post). Correct the sync issue to allow for reliable operation. | 9/9/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The unit was not running at the time of annual inspection. A full annual inspection shall be scheduled for 2020 once the elevator is operational. | 10/13/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 1/26/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency lighting shall be operational. | 1/7/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm shall be operational. | 1/7/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/17/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV needs Cat 5 test. | 11/10/2022 |