Inspection
Inspection Details
Equipment ID
24264
24264
Inspection Date
1/11/2022
1/11/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
32505e18-de67-4d1a-8cff-722b64da85cb
32505e18-de67-4d1a-8cff-722b64da85cb
Location
Mendenhall Partnership, LLC
2315 Locust St, St. Louis, MO
Phone: (314) 698-3597
Email: nicole@risetothelocation.com
2315 Locust St, St. Louis, MO
Phone: (314) 698-3597
Email: nicole@risetothelocation.com
Owner
Attn: Jassen
Mendenhall Partnership LLC
2315 Locust St, Ste 2, St. Louis, MO 63103
Phone: (314) 698-3597
Email: jassen@risetothelocation.com
Mendenhall Partnership LLC
2315 Locust St, Ste 2, St. Louis, MO 63103
Phone: (314) 698-3597
Email: jassen@risetothelocation.com
Billing
Attn: Nicole
Mendenhall Partnership LLC
2315 Locust St, Ste 2, St. Louis, MO 63103
Phone: (314) 698-3597
Email: nicole@risetothelocation.com
Mendenhall Partnership LLC
2315 Locust St, Ste 2, St. Louis, MO 63103
Phone: (314) 698-3597
Email: nicole@risetothelocation.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Test the machine room heat detectors. | 3/7/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | No | No | The Phase 1 visual indicator does not work. | 3/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | No | No | A maximum runby sign is required. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.9 - Power closing of doors or gates | 8.11.2.1.1(i) | No | No | The door time label has not been completed. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle hangers. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle fire gib. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | The governor switch does not function. Elevator Red Tagged. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 1/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle hangers. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway doors are missing the middle fire gib. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a current state operating certificate in the machine room. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Maintenance/repair records and fire service monthly testing checklist are missing. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Install the center hoistway door hangers at all floors. | 3/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Install the center fire gibs on all hoistway doors. | 3/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | MO State operating certificate not located in the machine room. |