Inspection
Inspection Details
Equipment ID
6505
6505
Inspection Date
1/31/2022
1/31/2022
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Michael Collumbien
Michael Collumbien
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
External ID
6ebe7984-131e-4e4c-930a-f9ff08850689
6ebe7984-131e-4e4c-930a-f9ff08850689
Location
Extended Stay America
5555 Veterans Memorial Pkwy, St. Peters, MO
Phone: (636) 976-2800
5555 Veterans Memorial Pkwy, St. Peters, MO
Phone: (636) 976-2800
Owner
Attn: ESA Management c/o Lerch Bates
ESA Management c/o Lerch Bates
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (303) 795-7956
Email: Extendedstay.elevators@lerchbates.com
ESA Management c/o Lerch Bates
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (303) 795-7956
Email: Extendedstay.elevators@lerchbates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Alarm bell not working | 4/30/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site posted on controller | 3/9/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 4/16/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Make arrangements to test lobby smoke detectors--failed to simulate smoke detectors | 4/16/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | 2.8.2.1 - A duplex GFCI receptable shall be provided in the machine room. | 4/23/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car telephone shall be operational. The phone has a dial tone, but it appears to be restricted and will not dial out. The phone monitor has been tested and meets requirements. | 4/23/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | 2.2.5.1 - The pit lighting shall provide an illumination of not less than 10 fc at the pit floor. New pit lighting was installed, but it does not meet illumination requirements. | 4/23/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | 2.8.2.1 - Feeder locations for the main and lighting branch circuits shall be marked on the main and lighting disconnects. | 4/23/2024 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of section 8.7. | 4/23/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | 2.27.3.2.1(c) - The smoke detector in the overhead shall be removed. There are no sprinklers in the hoistway. | 4/23/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not programmed to dial out. | 12/12/2025 |