Inspection
Inspection Details
Equipment ID
1451
1451
Inspection Date
2/9/2022
2/9/2022
Inspection Type
Alteration
Alteration
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Nick Huzar
Nick Huzar
Relief Valve Pressure
340
340
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
b645921f-6b78-4e37-add8-5a49a922514c
b645921f-6b78-4e37-add8-5a49a922514c
Location
Macy's- West Store / #652
2 W COUNTY CTR # 120012, SAINT LOUIS, MO
Phone: (314) 966-0017
2 W COUNTY CTR # 120012, SAINT LOUIS, MO
Phone: (314) 966-0017
Owner
Attn: Cathie Sherman
MACY'S MSOC VERTICAL COMPLIANCE
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (732) 734-3438
Email: Cathie.Sherman@macys.com
MACY'S MSOC VERTICAL COMPLIANCE
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (732) 734-3438
Email: Cathie.Sherman@macys.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair pit light | 6/15/2020 |
| conversion | conversion | n/a | No | No | Install inspection port on pump valve | 6/15/2020 |
| conversion | conversion | n/a | No | No | Replace leaking jack packing | 6/15/2020 |
| conversion | conversion | n/a | No | No | Clean pit & remove oil from pit floor | 6/15/2020 |
| conversion | conversion | n/a | No | No | Install year test tag on governor | 6/15/2020 |
| conversion | conversion | n/a | No | No | Clean car top--oil | 6/15/2020 |
| conversion | conversion | n/a | No | No | Rep[air emergency light in car | 6/15/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency light in car | 11/19/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | Clean pit remove oil rom floor, repair pit liht | 11/19/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. Remove oil from pit floor. repair pit light, clean oil off car top this is a reinspection item within 30 days max | 3/5/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/5/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 3/5/2026 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Replace control valve discharge hose | 3/5/2026 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | OSV needs to be tested, tagged & sealed. | 8/1/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and document on the log in the machine room. Remove gage and supply valve install test port | 3/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Provide test procedures in the maintenance control procedures | 3/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 3/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 10/16/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in the machine room | 3/5/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 3/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | provide testing procedures in the Maintenance control program | 3/5/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/5/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 3/5/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | Yes | Perform monthly fire service test and post on log in machine room. | 3/5/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post current MO State operating certificate in machine space. | 3/5/2026 |