Inspection
Inspection Details
Equipment ID
22275
22275
Inspection Date
11/9/2021
11/9/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
570
570
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
6446d753-3fdb-4243-9d01-00465b3dd37c
6446d753-3fdb-4243-9d01-00465b3dd37c
Location
Residence @ New Longview Apt
3341 SW Kessler Dr, Lee's Summit, MO
Phone: (000) 000-0000
3341 SW Kessler Dr, Lee's Summit, MO
Phone: (000) 000-0000
Owner
Attn: Amanda Middaugh
JVM Realty
3301 SW Kessler Dr, Lee's Summit, MO 64081
Phone: (816) 767-9999
Email: amiddaugh@jvmrealty.com
JVM Realty
3301 SW Kessler Dr, Lee's Summit, MO 64081
Phone: (816) 767-9999
Email: amiddaugh@jvmrealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | repair door restrictor it is missing parts | 11/13/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post log in the Machine Room. | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Repair the car door restrictor, it does not work, parts missing | 10/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | the stop switch in the fire service panel blows a fuse when activated | 10/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | monthly fire service test log in the machine room is not being filled out monthly | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post copy of the state operating certificate in the machine room | 1/1/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year | 12/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the elevator machine room expired in 2018, update with a copy of the current certificate annually | 7/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | elevator cab only has one working ceiling light bulb, required to have minimum working light bulbs, replace burnt out bulbs | 7/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate in the machine room expired in 2018, update with the new certificate annually | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.4 - Hoistway door locking devices | 2.12 | Yes | No | Top landing hoistway Unlocking device is off and lying on the car top | 11/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate in the machine room expired in 2022, update with the new certificate annually | 11/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Machine room air conditioning unit is not working, it’s flashing an error. Do not find a remote to operate the air conditioning unit in the machine room. | 10/28/2025 |