Inspection
Inspection Details
Equipment ID
7905
7905
Inspection Date
11/22/2021
11/22/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
3"
3"
Governor Rope Pull
50/210
50/210
Door Closing Force
NA
NA
External ID
b922d60c-2665-4ced-ad2c-5e4b637230bc
b922d60c-2665-4ced-ad2c-5e4b637230bc
Location
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO
Phone: (000) 000-0000
4960 Laclede Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Royals Oak
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Richard.Woolard@reachltc.com
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Richard.Woolard@reachltc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Properly guard the pit light. | 5/12/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | The car top shall have a code compliant emergency exit. | 5/12/2023 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | Re-socket hoist ropes on drum machine per A17.1 - 1996 Rule 1206.3 | 5/12/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Car top shall have a code compliant emergency exit. | 5/12/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean. Clean the pit. | 5/12/2023 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The machine room shall be cleaned. | 5/12/2023 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | Re-socket hoist ropes on drum machine per A17.1 - 1996 Rule 1206.3 | 5/12/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Car top shall have a code compliant emergency exit. | 5/12/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 5/12/2023 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | Wire ropes on drum-type machines shall be re-socketed in compliance with ASME A17.1 1996 edition, Rule 1206.3. | 5/12/2023 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The test is incomplete. The following testing items remain: pull out/pull thru of governor, governor switch and jaw, governor full load test of car safeties, buffer and counterweight buffer test. | 11/22/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 5/12/2023 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | Wire ropes on drum-type machines shall be re-socketed in compliance with ASME A17.1 1996 edition, Rule 1206.3. | 5/12/2023 |