Inspection
Inspection Details
Equipment ID
15848
15848
Inspection Date
8/1/2018
8/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
26
26
External ID
025ac9de-c9a7-49c4-a7e7-c498fbb6a45b
025ac9de-c9a7-49c4-a7e7-c498fbb6a45b
Location
King Bee Condos
1709 WASHINGTON AVE, SAINT LOUIS, MO
1709 WASHINGTON AVE, SAINT LOUIS, MO
Owner
King Bee Condo Association
1709 WASHINGTON AVE, SAINT LOUIS, MO 63103-1729
1709 WASHINGTON AVE, SAINT LOUIS, MO 63103-1729
Billing
Attn: Newton Management
1709 WASHINGTON AVE STE 505, SAINT LOUIS, MO 63103-1729
1709 WASHINGTON AVE STE 505, SAINT LOUIS, MO 63103-1729
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection is required. | 8/1/2018 |
| conversion | conversion | n/a | No | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. | 11/13/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/1/2018 |
| conversion | conversion | n/a | No | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the ?off? position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. | 11/13/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elvator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Re-inspection is required. | 9/14/2018 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | The car door restrictor device shall be repaired so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Re-inspection is required. | 9/14/2018 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Hoist ropes are rouged and approaching minimum diameter. Replace within 90 days. | 7/29/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency phone shall work. | 7/29/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/14/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/28/2023 |