Inspection
Inspection Details
Equipment ID
4217
4217
Inspection Date
8/22/2018
8/22/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Jeff Stanley
Jeff Stanley
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
01f028c9-fc94-4c34-8b71-968201e7f25a
01f028c9-fc94-4c34-8b71-968201e7f25a
Location
Davis Memorial Center
1900 S BROADWAY, OAK GROVE, MO
1900 S BROADWAY, OAK GROVE, MO
Owner
Oak Grove Senior Citizens Center
PO BOX 403, OAK GROVE, MO 64075-0403
PO BOX 403, OAK GROVE, MO 64075-0403
Billing
Attn: Oak Grove Senior Citizens Center
PO BOX 403, OAK GROVE, MO 64075-0403
PO BOX 403, OAK GROVE, MO 64075-0403
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Repair the emergency phone | 6/16/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | current cirt. not displayed | 8/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | macnine. room door not self closing or self locking | 8/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | no fire extinquisher in mach. room | 8/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | no wiring dia on site | 8/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | no on site maint records | 8/10/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | 8/10/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | remove oil return lines from jack to tank in machroom an put them in buckets in the pit | 8/10/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | excessive leakin replace packing | 8/10/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | pit has oil covering floor | 8/10/2026 |
| A17.1-2016 : Elevators | 2.31 - Relief Valves | 8.6.5.14.1 | Yes | No | unable to perform test |