Inspection
Inspection Details
Equipment ID
20138
20138
Inspection Date
8/1/2018
8/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Timothy Robinson
Timothy Robinson
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
20/8
20/8
External ID
86d114ef-797c-4a0d-8ba7-f670b794c16b
86d114ef-797c-4a0d-8ba7-f670b794c16b
Location
Edmond Office Plaza
902 EDMOND ST, SAINT JOSEPH, MO
902 EDMOND ST, SAINT JOSEPH, MO
Owner
Marks-Booker Enterprises, Inc
20130 COUNTY ROAD 355, SAINT JOSEPH, MO 64505-8521
20130 COUNTY ROAD 355, SAINT JOSEPH, MO 64505-8521
Billing
Attn: Marks-Booker Enterprises, Inc
20130 COUNTY ROAD 355, SAINT JOSEPH, MO 64505-8521
20130 COUNTY ROAD 355, SAINT JOSEPH, MO 64505-8521
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair/replace the car top inspection station, the inspecion switch is broken off and missing. can not put car on inspection at the car top inspection station | 5/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | one of the two emergency lights did not work | 10/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | The hoistway side of the hall doors need to be numbered | 5/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | need to have written procedures on how to perform annual tests and 5 year tests | 5/27/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform pressure relief test | 9/8/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.3.2.2 Cylinders Test shall be performed | Yes | No | Perform cylinder test | 9/8/2026 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)2(D) | Yes | No | Need to seal relief valve on hydraulic machine | 9/8/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.8 | Yes | No | Replace single bottom cylinder. Car safeties installed years ago. No variance on record and building owner could not provide documentation of a variance. | 9/8/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Door force exceeds 30 # | 9/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light has a defective lamp | 9/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door shall be self-closing and self-locking | 9/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 9/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Number hoistway side of hall doors | 9/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace broken top of car inspection switch. | 9/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan in machine room | 9/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records in machine room | 9/8/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 9/8/2026 |