Inspection
Inspection Details
Equipment ID
21604
21604
Inspection Date
8/8/2018
8/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
f18b4e63-358b-4eb9-ba11-5936cec1816e
f18b4e63-358b-4eb9-ba11-5936cec1816e
Location
Missouri Valley College
500 E COLLEGE ST, MARSHALL, MO
500 E COLLEGE ST, MARSHALL, MO
Owner
Missouri Valley College
500 E COLLEGE ST, MARSHALL, MO 65340-3109
500 E COLLEGE ST, MARSHALL, MO 65340-3109
Billing
Attn: Missouri Valley College
500 E COLLEGE ST, MARSHALL, MO 65340-3109
500 E COLLEGE ST, MARSHALL, MO 65340-3109
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | machine room fire extinguisher inspection tag is past due, get exinguisher inspected annually | 12/4/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Machine room light switch shall not be on a timer or motion switch | 12/4/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | replace the top of hoistway smoke detector that has been removed, it is requred because the pit has a sprinkler | 8/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | the smoke detector for the bottom landing lobby has a plastic cover that needs to be removed | 8/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | replace burnt out cab ceiling lights, does not meet minimum illumination | 12/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | repair door restrictor, it is missing parts | 3/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | machine room fire extinguisher has not been serviced since 2017 | 12/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | do not store non-elevator related material in the machine room | 12/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | monthly fire service test log is not being filled out in the machine room | 12/17/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log is not being filled out monthly | 12/1/2021 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.11.3.1.2(h) | No | No | non-elevator related material is not to be stored in the machine room | 12/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top | 2/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing car identification number inside the cab | 2/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Missing fire egress signage at all floors | 2/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing car identification number in cab on car panel 2.29.1.2 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing car identification number on jamb at main egress 2.29.1.2 |