Inspection
Inspection Details
Equipment ID
21603
21603
Inspection Date
8/8/2018
8/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
14
14
External ID
225abded-bc75-4dd8-a035-05dbd9139019
225abded-bc75-4dd8-a035-05dbd9139019
Location
Missouri Valley College
500 E COLLEGE ST, MARSHALL, MO
500 E COLLEGE ST, MARSHALL, MO
Owner
Missouri Valley College
500 E COLLEGE ST, MARSHALL, MO 65340-3109
500 E COLLEGE ST, MARSHALL, MO 65340-3109
Billing
Attn: Missouri Valley College
500 E COLLEGE ST, MARSHALL, MO 65340-3109
500 E COLLEGE ST, MARSHALL, MO 65340-3109
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | repair machine room door closer it has been ripped out of the door and the door does not self close | 12/4/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | machine room fire extinguisher tag is past due, have the extinguisher tested and tagged annually | 12/4/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | The smoke detector at the top of the hoistway needs to be replaced. it has been removed and hasn't been replaced. The detector at the top of the hoistway is required because the pit has a sprinkler. | 8/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | do not store non-elevator related material in the machine room | 12/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | machine room fire extinguisher has not been serviced since 2017 | 12/17/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log is not being filled out monthly | 12/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | alarm bell button only works intermittently, repair or replace alarm bell button (A17.1 227.1) | 2/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing car identification number on jamb at main egress | 2/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing car identification number inside the cab | 2/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | Missing fire service egress signage at all floors | 2/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing car identification number on jamb at main egress 2.29.1.2 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Missing unit number inside the cab on the car panel 2.29.1.2 |