Inspection
Inspection Details
Equipment ID
13029
13029
Inspection Date
8/23/2018
8/23/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Steven Meehan
Steven Meehan
Relief Valve Pressure
Slide
8 ins
8 ins
Governor Rope Pull
600
600
Door Closing Force
20
20
External ID
794ab766-5a1e-4155-94f2-f4433c3ec574
794ab766-5a1e-4155-94f2-f4433c3ec574
Location
Cass County Justice Center
2501 W MECHANIC ST, HARRISONVILLE, MO
2501 W MECHANIC ST, HARRISONVILLE, MO
Owner
Cass County Justice Center
2501 W WALL ST, HARRISONVILLE, MO 64701-1797
2501 W WALL ST, HARRISONVILLE, MO 64701-1797
Billing
Attn: Cass County Commissioners
2501 W MECHANIC ST, HARRISONVILLE, MO 64701-7804
2501 W MECHANIC ST, HARRISONVILLE, MO 64701-7804
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | less than 6 ins. of runby | 8/14/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarmbell not working | 8/14/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emg lt not working | 9/9/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | no sump pump in pit no drain 106.1b(3) | 10/25/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | no sump pump cover. 106.1b(4) | 10/25/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 9/21/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg. phone not working | 11/5/2021 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | run by less than 6 inches | 11/5/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emg. phone not working | 1/7/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE WORKING PHONE (DIALS BUT HANGS UP WHEN MESSAGE STARTS) | 9/12/2025 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Door restrictor did not work, adjust door restrictor so it works | 8/7/2026 |