Inspection
Inspection Details
Equipment ID
19558
19558
Inspection Date
3/3/2022
3/3/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Paul Jaremko
Paul Jaremko
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
f4362abf-57f4-4310-b291-5987f98dfa92
f4362abf-57f4-4310-b291-5987f98dfa92
Location
San Regis Apartments
1015 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 233-4513
1015 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 233-4513
Owner
Attn: Cathy Chavez
San Regis Apartments
1015 Faron St, St. Joseph, MO 64501
Phone: (816) 233-3002
Email: sanregis@molinemgt.com
San Regis Apartments
1015 Faron St, St. Joseph, MO 64501
Phone: (816) 233-3002
Email: sanregis@molinemgt.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate. | 5/1/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell does not operate. | 12/20/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Water is leaking through the top of the hoistway enclosure and onto the top of the elevator. | 2/15/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Machine room door needs to be self locking and non-defeatable. | 2/15/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside machine room | 2/15/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not provide two way communication | 2/15/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | Gas powered snowblower, container of gasoline, and bags of salt must be removed from elevator machine room. Non-elevator related material shall not be stored inside the machine room. Extreme fire hazard. | 2/15/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | x | No firefighter phase 2 operation panel behind locked cover on car operating panel. | 3/24/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | No hoistway access operation provided. | 12/28/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 8.11.3.1.5(f) | Traveling cable needs to be replaced. Traveling cable is damaged due to moisture issue. | 12/28/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | Identify the inside of hoistway doors with a numeral | 12/28/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Post In Case of Fire Do Not Use Elevator signage next to hall button fixture at bottom landing. | 12/28/2022 | ||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No maintenance control plan on site | 12/28/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | Identify inside of the hoistway door with a numeral | 4/17/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed | 4/17/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | x | 2.27.3.3.1(c) Door close button non functional must reinspect when issue is corrected. | 3/29/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | PROVIDE A WORKING IN CAR EMERGENCY PHONE | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | x | BATTERY ENERGENCY LOWERING NOT WORKING |