Inspection
Inspection Details
Equipment ID
14371
14371
Inspection Date
7/26/2018
7/26/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
56304cad-2094-477f-ad65-a362bc6a32ec
56304cad-2094-477f-ad65-a362bc6a32ec
Location
Administration Bldg
1964 PRAIRIE DELL RD, UNION, MO
1964 PRAIRIE DELL RD, UNION, MO
Owner
East Central College
1964 PRAIRIE DELL RD, UNION, MO 63084-4344
1964 PRAIRIE DELL RD, UNION, MO 63084-4344
Billing
Attn: East Central College
1964 PRAIRIE DELL RD, UNION, MO 63084-4344
1964 PRAIRIE DELL RD, UNION, MO 63084-4344
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room light switch shall be a toggle type switch. The machine room light switch shall not be motion activated type. | 12/5/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/28/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/1/2022 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | The machine room light switch shall be a toggle type switch. The machine room light switch shall not be motion activated. | 12/5/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 12/5/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cartop has bolts (ceiling thru bolts) sticking up >2". This is a tripping hazard. | 12/5/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. Repair or replace. | 8/22/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate is expired. | 12/5/2024 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 112.4(b) | Yes | No | Door pressure shall not exceed 30 lbs. | 9/22/2025 |