Inspection
Inspection Details
Equipment ID
15909
15909
Inspection Date
2/23/2022
2/23/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
8875b80e-aecf-4b18-8e88-2068404911cd
8875b80e-aecf-4b18-8e88-2068404911cd
Location
Hamilton Apartments
956 Hamilton Ave, St. Louis, MO
Phone: (314) 361-5600
956 Hamilton Ave, St. Louis, MO
Phone: (314) 361-5600
Owner
Attn: Hamilton Apartments
Hamilton Apartments
707 Sable Oaks Dr, South Portland, ME 41066
Phone: (000) 000-0000
Hamilton Apartments
707 Sable Oaks Dr, South Portland, ME 41066
Phone: (000) 000-0000
Billing
Attn: Preservation Management
Preservation Management
956 Hamilton Ave, St. Louis, MO 63112
Phone: (000) 000-0000
Preservation Management
956 Hamilton Ave, St. Louis, MO 63112
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean and dry. | 1/22/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Water and oil shall not be allowed to accumulate on pit floors. | 6/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/22/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 6/22/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Water and oil shall not be allowed to accumulate on pit floors. | 6/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/22/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 6/22/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The in-car keyed stop switch shall be tested as required. The key couldn't be located, therefore the switch wasn't tested. | 9/14/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 5/5/2025 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 302.3 | Yes | Yes | During the inspection, signigicant leakage of hydraulic fluid was observed at the cylinder jack packing glad. The hydraulic jack esperienced a blown packing seal, causing loss of system pressure and uncontrolled movment. Unit has been red tagged and shall be repaired. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car phone, emergency ligh and bell shall be functional. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Pit shall be clean and dry. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Yes | No | Fire service phase I and II remain to be tested. |