Inspection
Inspection Details
Equipment ID
1747
1747
Inspection Date
3/4/2022
3/4/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
19 / 23
19 / 23
External ID
324bd9d9-c8af-4dd6-a570-830a5e3bb4cf
324bd9d9-c8af-4dd6-a570-830a5e3bb4cf
Location
St. Louis Altenheim
5408 S BROADWAY, SAINT LOUIS, MO
Phone: (314) 353-7225
5408 S BROADWAY, SAINT LOUIS, MO
Phone: (314) 353-7225
Owner
St. Louis Altenheim
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
Billing
Attn: St. Louis Altenheim
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.1 | Yes | No | Counterweight runby is 1". Minimum required is 6" | 4/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE SHALL ALLOW FOR 2-WAY COMMUNICATION. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | Yes | No | Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking . Door does not latch. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine room lighting needs to be repaired, 1 or more bulbs not working. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. (Expired) | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service Testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Hoistway door has loose guide on 2R floor. Repair/replace as needed. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Hoist Ropes are dry and showing “rouge” and "dusting" on floor. Ropes shall be cleaned and lubricated per OEM recommendations | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.4 | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track.(all floors). | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | Yes | No | Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". | 8/31/2026 |