Inspection
Inspection Details
Equipment ID
1661
1661
Inspection Date
3/8/2022
3/8/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
30da524e-df5c-4ebe-9ddc-e833994a9780
30da524e-df5c-4ebe-9ddc-e833994a9780
Location
10 South Broadway Bldg
10 S Broadway, St. Louis, MO
Phone: (314) 421-3480
10 S Broadway, St. Louis, MO
Phone: (314) 421-3480
Owner
Attn: Hertz Investment Group
Hertz Investment Group
10 S Broadway, Ste 100, St. Louis, MO 63102
Phone: (314) 421-3480
Email: jkoncki@hertzgroup.com
Hertz Investment Group
10 S Broadway, Ste 100, St. Louis, MO 63102
Phone: (314) 421-3480
Email: jkoncki@hertzgroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | Yes | Phase 1 Fire Return no working. Did not red tag. | 2/14/2019 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 210.2 | No | No | Need hoist door straps and gate straps. | 9/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car top inspection station was not checked. | 8/9/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Top of car could not be tested. No pull chain keys on site. | 3/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Pit could not be inspected. No pull chain keys on site. Do not know if there is an OSV | 3/8/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator phone does not work on normal or 110v emergency power or normal power | 10/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair inoperative emergency light | 12/23/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 7/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 7/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 7/14/2025 |
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | 111.9e The hoistway door unlocking device at the bottom landing shall be repaired as designed to allow safe access to the pit. | 9/3/2025 |