Inspection
Inspection Details
Equipment ID
20667
20667
Inspection Date
3/2/2022
3/2/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25F/25R
25F/25R
External ID
ec211b7c-4e44-4049-9796-8e8530afa910
ec211b7c-4e44-4049-9796-8e8530afa910
Location
Power Plant City Hospital
1419 Carrol St, St. Louis, MO
Phone: (314) 333-4559
1419 Carrol St, St. Louis, MO
Phone: (314) 333-4559
Owner
Attn: Scott Bopp, Property Manager
Tucker Lafayette Partners, LLC c/o Cozad Property Management Company
16 Sunnen Dr, Ste 164, St. Louis, MO 63143
Phone: (314) 480-4683
Email: sbopp@cozadgroup.com
Tucker Lafayette Partners, LLC c/o Cozad Property Management Company
16 Sunnen Dr, Ste 164, St. Louis, MO 63143
Phone: (314) 480-4683
Email: sbopp@cozadgroup.com
Billing
Attn: Louie Tocco, Director of Property Management
Tucker Lafayette Partners, LLC c/o Cozad Property Management Company
16 Sunnen Dr, Ste 164, St. Louis, MO 63143
Phone: (314) 480-4683
Email: ltocco@cozadgroup.com
Tucker Lafayette Partners, LLC c/o Cozad Property Management Company
16 Sunnen Dr, Ste 164, St. Louis, MO 63143
Phone: (314) 480-4683
Email: ltocco@cozadgroup.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures, maintenance charts, and fire service monthly testing log are missing. | 2/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | The door open button shall be operational on Phase 2 fire service. | 2/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing shall be documented monthly. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Hoist ropes appear dry and showing moderate rouge. Ropes shall be cleaned and lubricated per OEM recommendations. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | 2.20.9.4 - Hoist rope tail retaining clips shall be properly spaced. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. There are puddles of oil around rails/debris. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | No | No | Governor rope shall be shortened/replaced to allow proper tension device clearance. Sheave almost touching safety switch. | 3/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | Suspension ropes shall be replaced due to severe rouging(rusting) and insufficient/reduced actual diameter as measured with "No-Go" rope gauge. | 4/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Violation: No 2026 MCP documentation onsite. | 4/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service Testing shall be documented monthly. | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean cartop. Previously cited violation | 4/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Puddles of oil around rails / debris. Previously cited violation. | 4/10/2026 |