Inspection
Inspection Details
Equipment ID
12533
12533
Inspection Date
3/4/2022
3/4/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
e56b1f5c-cd4f-4826-81d2-432f970f7a1f
e56b1f5c-cd4f-4826-81d2-432f970f7a1f
Location
Forest Park Community College
5600 Oakland Ave, St. Louis, MO
Phone: (618) 978-5176
5600 Oakland Ave, St. Louis, MO
Phone: (618) 978-5176
Owner
Attn: John Duarte
St. Louis Community College
3221 McKelvey Road, Suite 100 ,Bridgeton, MO 63044
Phone: (314) 435-9505
Email: apayable@stlcc.edu
St. Louis Community College
3221 McKelvey Road, Suite 100 ,Bridgeton, MO 63044
Phone: (314) 435-9505
Email: apayable@stlcc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | The emergency light shall work. | 1/30/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | A fire extinguisher is required in the machine room. | 1/30/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Pipes conveying liquid, gas, or vapor located above the elevator equipment in the machine room shall be guttered or guarded to prevent damage to equipment. | 1/30/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | Pipes conveying liquid, gas, or vapors shall not be located in the hoistway. | 1/30/2020 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display the current state operating certificate in the machine room. | 1/30/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean and dry. Remove the water from the pit. | 3/30/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 3/30/2022 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/16/2023 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Pipes carrying liquid, vapor, or gas that come in close proximity to elevator equipment shall be guarded or guttered. | 3/16/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working. | 5/5/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher is expired. | 6/21/2023 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No certificate in machine room. | 6/21/2023 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Emergency lowering unit is not working. | 5/5/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/5/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: There is no testing tag on the extinguisher. | 8/7/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/6/2025 |