Inspection
Inspection Details
Equipment ID
6085
6085
Inspection Date
3/1/2022
3/1/2022
Inspection Type
Alteration
Alteration
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Patrick Goessling
Patrick Goessling
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
de8a9b62-81ad-43ec-aa33-f80639288a4a
de8a9b62-81ad-43ec-aa33-f80639288a4a
Location
Arch Hotel Project Owner LLC
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
Owner
Attn: Hank Hermes, Director of Engineering
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Bottom demarcation lights don't work | 5/1/2019 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(D) | No | No | Replace broken step tread. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Written maintenance control program shall be provided on-site for each elevator. | 12/19/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | No | Yes | Lower escalator brake torque is only 64 ft lbs. Minimum is 125 ft lbs. Replace escalator brake. Escalator removed from service & red tagged. Re-inspection required before use | 2/22/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | No | No | Broken comb plate at the bottom shall be replaced | 3/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace broken step tread. Re-inspection required | 3/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Unit needs complete cleandown | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | Yes | Most, if not all, step treads have damaged fins on treads, causing sharp edges and excessive gaps between fins. Red-tagged, Re-inspection required | 10/2/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | Yes | Yes | Bottom brake torque is below minimum. Red-tagged, Re-inspection required | 10/2/2024 |
| A17.1-2016 : Elevators | 9.16 - Ceiling intersection guards | 8.6.8.9 | No | No | Replace anti climbing barricade on outer decking between units at lower end | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 Escalator Entrance and Egress Ends | No | No | Walkoff plate at egress end had missing/broken support braces underneath, need to be replaced | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/29/2024 |