Inspection
Inspection Details
Equipment ID
9349
9349
Inspection Date
9/20/2017
9/20/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Zelle
Robert Zelle
Mechanic Name
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
Location
Woener School
6131 Leona, St. Louis, MO
Phone: (314) 633-9103
6131 Leona, St. Louis, MO
Phone: (314) 633-9103
Owner
St.Louis Board of Education
801 N, 11th St., St. Louis, MO 63101
801 N, 11th St., St. Louis, MO 63101
Billing
Attn: Advanced Elevator
P.O. Box 423, , MO 64601
P.O. Box 423, , MO 64601
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 6/4/2026 |
| conversion | conversion | n/a | No | No | Machine room door shall be self-locking. | 6/4/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | The in car stop switch has a broken mounting bezel. The stop switch shall be repaired. | 6/21/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 9/2/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The relief pressure shall be tested. | 9/2/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | The door closing force shall be tested. | 6/4/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 11/3/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operable | 5/23/2024 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | Yes | Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required. | 8/14/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | Yes | Yes | Upon re-inspection, found control valve had been replaced without alteration permit being issued. Elevator still dropped 1 3/4" during three 15 minute standing tests with shut off valve closed. Oil level in tank remained unchanged each time. Left unit Red-tagged. Re-inspection required | |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required. |