Inspection
Inspection Details
Equipment ID
80
80
Inspection Date
8/27/2018
8/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
20/18
20/18
External ID
7ca5a31b-38c1-4458-b112-3840df7a8343
7ca5a31b-38c1-4458-b112-3840df7a8343
Location
St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO
2016 S MAIN ST, MARYVILLE, MO
Owner
St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO 64468-2655
2016 S MAIN ST, MARYVILLE, MO 64468-2655
Billing
Attn: St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO 64468-2655
2016 S MAIN ST, MARYVILLE, MO 64468-2655
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 9/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Provide lighting in machine room. Existing feed for machine lights has no electrical power | 2/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. | 11/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Identify inside of hoistway doors with a numeral corresponding to landing floor. | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform emergency standby operation with an inspector present. | 8/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide "Elevator Emergency Power" signal at the lobby of the designated landing. | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Replace pit sprinkler head with sidewall sprinkler head located within 24 inches of pit floor | 11/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Test emergency power operation with inspector present | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | REPAIR PIT LIGHTING | 10/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | FRONT DOOR TORQUE IS >30lbs | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 2.26.2 | Yes | No | DOWN LIMIT DID NOT WORK | 1/16/2026 |