Inspection
Inspection Details
Equipment ID
79
79
Inspection Date
8/27/2018
8/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
24/20
24/20
External ID
0d045def-f510-4c0f-be71-175e95e14b9e
0d045def-f510-4c0f-be71-175e95e14b9e
Location
St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO
2016 S MAIN ST, MARYVILLE, MO
Owner
St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO 64468-2655
2016 S MAIN ST, MARYVILLE, MO 64468-2655
Billing
Attn: St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO 64468-2655
2016 S MAIN ST, MARYVILLE, MO 64468-2655
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 9/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Provide means to disconnect car lighting in machine room. Existing disconnect has been bypassed. | 2/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. | 11/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Identify inside of doors with a numeral corresponding to landing floor. Numeral to be a minimum of 4 inches tall. | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test emergency standby operation with an inspector present. | 8/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide "Elevator Emergency Power" signal in the lobby at the designated landing | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate without normal power | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Replace pit sprinkler head with sidewall sprinkler head located within 24 inches from pit floor | 11/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Test emergency power with inspector present | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | FRONT DOOR TORQUE IS >30lbs | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.3 - Final and emergency terminal stopping devices | 2.25.3 | Yes | Yes | UP LIMIT NOT WORKING BEFORE WE HIT THE STOP RING | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | IN CAR EMERGENCY PHONE IS WORKING UNDER NORMAL CONDITIONS BUT NOT WORKING ON BATTERY BACK-UP | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | CAR DOOR DOES NOT STAY OPEN ON PHASE 2 FIRE SERVICE | 1/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | IN CAR PHONE IS WORKING UNDER NORMAL POWER CONDITIONS BUT NOT WORKING UNDER BATTERY BACKUP CONDITIONS | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | CAR DOORS WILL NOT STAY OPEN DURING PHASE 2 FIRE SERVICE |