Inspection
Inspection Details
Equipment ID
19158
19158
Inspection Date
3/7/2022
3/7/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
b8b3a66a-8d1a-487d-b2cc-a7694edb0ef7
b8b3a66a-8d1a-487d-b2cc-a7694edb0ef7
Location
Aspire School of Confluence
5421 THEKLA AVE, SAINT LOUIS, MO
Phone: (314) 241-1110
5421 THEKLA AVE, SAINT LOUIS, MO
Phone: (314) 241-1110
Owner
Attn: Michael Baker
Confluence Academy, Inc
611 N 10 St, Ste 525, St. Louis, MO 63101
Phone: (314) 588-8554 Ext: 7031
Email: mbaker@confluenceacademy.org
Confluence Academy, Inc
611 N 10 St, Ste 525, St. Louis, MO 63101
Phone: (314) 588-8554 Ext: 7031
Email: mbaker@confluenceacademy.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | The elevator pit floor is covered in oil and water. The elevator pit shall be kept clean and dry. | 11/30/2022 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 10/23/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work. | 3/7/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Place current state operating certificate in elevator machine room. | 11/30/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | ABC fire extinguisher required in elevator machine room. | 11/30/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 11/30/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 11/30/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 4/20/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | The lights in the cab are not working. The minimum illumination in the cab shall be no less than 5 foot-candles. | 11/30/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in-car emergency telephone shall be operational. | 9/25/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/29/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 11/29/2023 |