Inspection
Inspection Details
Equipment ID
8921
8921
Inspection Date
12/22/2021
12/22/2021
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
David Hill
David Hill
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
External ID
74147d57-5448-4db2-a47e-99488b14702a
74147d57-5448-4db2-a47e-99488b14702a
Location
Woodrail
Nifong & Forum, Columbia, MO
Phone: (573) 882-3639
Nifong & Forum, Columbia, MO
Phone: (573) 882-3639
Owner
Attn: Rick Sanders
University of Missouri Healthcare
1 Hospital Dr, Columbia, MO 65212
Phone: (573) 882-9929
Email: Rsb7z@umsystem.edu
University of Missouri Healthcare
1 Hospital Dr, Columbia, MO 65212
Phone: (573) 882-9929
Email: Rsb7z@umsystem.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 1/25/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a sump hole cover per 40-05.065 | 1/25/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide machine room lighting of not less than 10ft candles measured at the floor through out the entire machine room | 1/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Need elevator prints on site | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Excessive leaking during 15b minute set. Repair/replace control valve | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need code dat plate conforming to sec 8.9 | 12/14/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state certificate in machine room | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Excessive leaking during 15b minute set. Repair/replace control valve | 12/22/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Need to install non combustible sump hole cover, flush with pit floor | 1/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in machine room shall be a minimum of 10 foot candles to floor | 9/9/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to install a non-combustible sump hole cover flush with pit floor | 1/14/2025 |