Inspection
Inspection Details
Equipment ID
18283
18283
Inspection Date
2/28/2022
2/28/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Shaun Deckard
Shaun Deckard
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
c5da5dfd-eb14-446f-a2eb-ef76084d0ef6
c5da5dfd-eb14-446f-a2eb-ef76084d0ef6
Location
Creekside
2650 E 32ND ST, JOPLIN, MO
Phone: (417) 434-3990
2650 E 32ND ST, JOPLIN, MO
Phone: (417) 434-3990
Owner
Attn: Creekside Office Complex
Creekside Office Complex
3246 S HIGHLAND AVE, JOPLIN, MO 64804
Phone: (000) 000-0000
Email: gil_stevens@yahoo.com
Creekside Office Complex
3246 S HIGHLAND AVE, JOPLIN, MO 64804
Phone: (000) 000-0000
Email: gil_stevens@yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted in frame in machine room | 10/13/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No frame present | 8/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2015) | 8/5/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | S(1)/6.5.9.3/8.11.2.2.6. Fire service Door Open (Momentary/Peekaboo) shall work properly. (REINSPECTION REQUIRED) | 8/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Travel Cable insulation cracked in multiple places, exposing internal wiring. Should be replaced. | 8/5/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | S(1)/6.5.9.3/8.11.2.2.6. Fire service Door Open (Momentary/Peekaboo) shall work properly. (REINSPECTION REQUIRED) | 8/5/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No frame present | 8/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2015) | 8/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Travel Cable insulation cracked in multiple places, exposing internal wiring. Should be replaced. | 8/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. | 7/29/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in Machine Room. | 7/29/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking | 7/29/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept dry, water/oil in pit. Clean pit, inspect pit equipment , remove rust and paint equipment as needed. Investigate/repair water leak. | 7/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide mcp in machine room | 7/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Must make Fire Service Phase II operable. 8.11.2.26 | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Must provide Pit Ladder. I(%) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Must provide means to monitor oil loss from jack packing Glands. 8.6.5.5.2 |