conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The car door restrictor device needs to be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. This will require a reinspection for compliance.
|
3/5/2019
|
|
conversion
|
conversion
|
n/a
|
|
|
The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005.
|
10/1/2018
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required.
|
9/11/2019
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
9/11/2019
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005.
|
5/11/2020
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005.
|
5/11/2020
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)8
|
x
|
x
|
Overspeed governor jaw set at too high of a rate of speed, must be below 175 fpm. Red-tag & Re-inspection required
|
4/1/2022
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide guards on bulbs to prevent accidental contact or breakage.
|
4/5/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Cab floor tile is worn, has hole. Tripping hazard, replace.
|
4/5/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, have serviced or replaced
|
4/5/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide guards on machine room bulbs, to prevent accidental contact or breakage
|
4/5/2025
|