Inspection
Inspection Details
Equipment ID
11220
11220
Inspection Date
3/16/2022
3/16/2022
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Mark Zachgo
Mark Zachgo
Relief Valve Pressure
Slide
00
00
Governor Rope Pull
00
00
Door Closing Force
00
00
External ID
83be5a37-b47f-4528-b4a1-377ee296a1c3
83be5a37-b47f-4528-b4a1-377ee296a1c3
Location
Jackson County Courthouse
415 E 12th St, Kansas City, MO
Phone: (816) 881-3258
Email: bgaddie@jacksongov.org
415 E 12th St, Kansas City, MO
Phone: (816) 881-3258
Email: bgaddie@jacksongov.org
Owner
Attn: Jackson Co Courthouse Facilities Mgmt
Jackson Co Courthouse Facilities Mgmt
415 E 12th St, Kansas City, MO 64106
Phone: (816) 881-3258
Email: Bgaddie@jacksongov.org
Jackson Co Courthouse Facilities Mgmt
415 E 12th St, Kansas City, MO 64106
Phone: (816) 881-3258
Email: Bgaddie@jacksongov.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoisting ropes undersized. Min.594 actual .588 | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Seal penetration's and voids in hoistway walls | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Seal penetrations in machine space | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | Supply test of FFS devices | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 8.11.2.2.7 | Yes | No | Supply test of standby power(generator) | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Landing door jamb loose at B level. | 5/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 10/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Landing door jamb loose at basement level. | 10/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Yes | No | Provide an audible signal while in recall. | 5/19/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Yes | No | Provide an audible signal. | 5/21/2026 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Repair the door restrictor. | 5/21/2026 |
| A17.1-1996 : Elevators | 3.21 - Governor releasing carrier | 1001.2(c)(27) | Yes | No | The mini-ball is not releasing properly when the safties actuate. | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. |