Inspection
Inspection Details
Equipment ID
18014
18014
Inspection Date
3/17/2022
3/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
154c2c2c-0516-47b1-bd33-4e54e7c13590
154c2c2c-0516-47b1-bd33-4e54e7c13590
Location
HyVee- Maryville
1217 S Main St, Maryville, MO
Phone: (660) 582-2191
1217 S Main St, Maryville, MO
Phone: (660) 582-2191
Owner
Attn: Nate Jaster
HyVee Inc- Maryville
1217 S Main St, Maryville, MO 64468
Phone: (660) 582-2191
Email: njaster@hy-vee.com
HyVee Inc- Maryville
1217 S Main St, Maryville, MO 64468
Phone: (660) 582-2191
Email: njaster@hy-vee.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 3/17/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Replace burnt-out car lighting. | 3/27/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light fixture does not illuminate. No lamp in fixture. | 3/27/2026 |
| A17.1-1996 : Elevators | 2.37 Pressure switch | 306.14 Pressure switch | Yes | No | Install low pressure switch. Top of cylinder is above storage tank. | 3/17/2022 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate on controller or disconnect | 3/27/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | Test and log documentation of firefighter operation monthly. | 3/27/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate inside the machine room | 3/27/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 3/27/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions next to hall fire keyswitch | 3/27/2026 |
| A17.1-1996 : Elevators | 2.37 Pressure switch | 306.14 Pressure switch | Yes | No | Install low pressure switch on control valve. Cylinder head is above control valve. | 3/27/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No state operating certificate on site. Need to display the certificate inside the machine room | 3/27/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 3/29/2024 |
| A17.1-1996 : Elevators | 2.37 - Pressure Switch | 306.14 | Yes | No | Need to install low pressure switch on control valve | 3/29/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions next to hall fire keyswitch | 3/27/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Car light fixtures do not illuminate. | 3/27/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove hydraulic oil from pit sump hole. | 3/27/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 3/27/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency telephone not operational. Mandatory Re-inspetion due in 14 days. Alarm Bell works. | 3/12/2025 |
| A17.1-1996 : Elevators | 2.37 Pressure switch | 306.14 Pressure switch | Yes | No | When the top of the cylinder head is above the top of the storage tank a switch shall be provided to be incompliance with A17.1 section 306.14. | 3/12/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Car lighting worked upon arrival. When lighting disconnect was turned off light fixtures didn't light possible bad light ballast, | 3/27/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | The Phase I Operation Procedures shall be placed @ the Main Egress Location. | 3/27/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State Operating Certificate has not been available since 5/07/2020. | 3/27/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE A WORKING IN CAR EMERGENCY PHONE | 3/24/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working |