Inspection
Inspection Details
Equipment ID
3511
3511
Inspection Date
2/3/2022
2/3/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Eddie Sargent
Eddie Sargent
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
cbaedb8a-2653-45f3-baf1-4234a5798e53
cbaedb8a-2653-45f3-baf1-4234a5798e53
Location
Nowlin Middle School
2800 S Hardy Ave, Independence, MO
Phone: (816) 521-5380
2800 S Hardy Ave, Independence, MO
Phone: (816) 521-5380
Owner
Attn: Geri Frink
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | x | x | the fire service phase 1 keyswitch did not work, repair the keyswitch | 3/12/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | provide a record of findings for firefighters' service operation | 12/15/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/26/2022 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | the monthly firefighters service test log is not being filled out monthly | 1/26/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | the fire service relays in the machine room are hanging by their wires out of the electrical box, relays need to be properly secured to the electrical box | 1/26/2022 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | the fire hat jewel in the car operating panel did not light during phase 1 recall. | 1/26/2022 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | phase 1 fire service recall audible signal did not work | 1/26/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | label controller, tank, disconnects, car operating panel, pit and car top Elevator #3 | 1/26/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | does not have Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | emergency light battery is weak, the lights dim when the alarm button is pushed, the battery needs to be replaced | 8/23/2023 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | the monthly fire service test log in the machine room is not being filled out monthly | 10/27/2025 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | Replace burnt out cab ceiling lights, required to have 5 foot candles of illumination inside the elevator and minimum of two bulbs | 10/27/2025 | ||
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | Put new bulb in car top fixture and it didn’t work, repair car top work light fixture |