Inspection
Inspection Details
Equipment ID
6981
6981
Inspection Date
7/25/2018
7/25/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
d368fc76-30a0-4ea3-aea5-b055ed686037
d368fc76-30a0-4ea3-aea5-b055ed686037
Location
Hilton Frontenac
1335 S LINDBERGH BLVD, FRONTENAC, MO
1335 S LINDBERGH BLVD, FRONTENAC, MO
Owner
Frontenac Property Owner LLc
71 S WACKER DR STE 2130, CHICAGO, IL 60606-4666
71 S WACKER DR STE 2130, CHICAGO, IL 60606-4666
Billing
Attn: Frontenac Property Owner LLc
71 S WACKER DR STE 2130, CHICAGO, IL 60606-4666
71 S WACKER DR STE 2130, CHICAGO, IL 60606-4666
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace expired battery in door restrictor control box. | 11/7/2018 |
| conversion | conversion | n/a | No | No | Repair pit shut off valve that is leaking. | 11/7/2018 |
| conversion | conversion | n/a | No | No | Cylinder packing is leaking and requires repair. | 11/7/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Correct the various hydraulic leaks at the valve. | 10/15/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate. | 10/15/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The machine room shall not be used for the storage of non-elevator related materials. | 10/15/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. This valve was last tested in 2018. The overspeed valve shall be tested with the rated load on or before the next annual test. | 9/15/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV testing is incomplete due to oil damaged pump belts. A successful category 5 test of the overspeed valve shall be completed. | 7/24/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire service buzzer and fire hat shall work correctly, currently work intermittently. | 7/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 7/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time. | 12/17/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in the machine room. | 12/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace the oil soaked pump belts. | 12/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair leaky valve/pump. Habitual leaks, draining into hallway. | 12/17/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Provide documentation of a successful category 5 test of the overspeed valve. If documentation cannot be provided, the overspeed valve test is due now. Note: Overspeed valve test started on 8/14/23, but failed due to pump unit issue. Pump unit has since been replaced. | 12/6/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed valve testing incomplete: Testing crew was not able to get car speed up to setting speed. Adjustments shall be made and OSV shall re-tested. | 12/16/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Replace missing and damaged ceiling tiles. | 10/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | This unit has a clock built into the top of the hoistway which has an approved variance allowing the clock to remain. However the back cover is missing exposing light bulbs, plastic, and electrical wiring. The missing non-combustible cover shall be re-installed/provided. | 10/9/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Replace missing and damaged ceiling tiles. Violation to be certified as corrected by owner. | 10/20/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Yes | No | Non-elevator related items shall not be stored in Machine Room, including tables, and floor to ceiling shelving of flammable fabrics,etc..Photo documentation available. REINSPECTION TO ENFORCE | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Replace missing and damaged ceiling tiles. Violation to be certified as corrected by owner. Photo Documentation available. REINSPECTION TO ENFORCE | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. No Certificate displayed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. No Certificate displayed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP, 2 of 5 previous months in 2026 have been documented |