Inspection
Inspection Details
Equipment ID
22085
22085
Inspection Date
3/15/2022
3/15/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Aaron Bagley
Aaron Bagley
Relief Valve Pressure
950
950
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
18
18
External ID
e8a2b99f-c976-410b-8d5e-e1b1e68aad31
e8a2b99f-c976-410b-8d5e-e1b1e68aad31
Location
Kennard CJA
5031 POTOMAC ST, SAINT LOUIS, MO
Phone: (314) 633-9103
5031 POTOMAC ST, SAINT LOUIS, MO
Phone: (314) 633-9103
Owner
Attn: Rosmon Johnson
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Rosmon.Johnson@slps.org
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Rosmon.Johnson@slps.org
Billing
Attn: Cardinal Elevator
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: contact@cardinalelevator.com
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: contact@cardinalelevator.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.26 - Broken rope, chain, or tape switch | 8.11.2.1.3(i) | Yes | Yes | Replace slack chain switch. Switch has been wet and is corroded. | 8/27/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Pit equipment is rusted. Correct source of water backup. | 10/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.3.4.1 | Yes | No | A category 5 full load test is required in 2019. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.5 | Yes | Yes | The door open button shall be operational on fire service | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Phase 1 & Phase 2 fire service key switches shall be keyed the same. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | The keys were not on-site. Could not check COP stop switch or phase 2 fire service. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | No | No | Car door open button shall be operational. | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Phase 1 fire recall shall be operational. (Violation corrected 12/3/2020) Re-Inspection Pending | 3/15/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | No | No | Car door open button shall operate | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Keys to operate unit shall be available, unable to verify Phase II, no keys. Re-inspection required | 1/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A written MCP shall be kept in the machine room for each unit | 11/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to test safeties due to no documentation. Re-inspection required | 1/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | No | No | Provide car door open button to work. (Pushing floor number opens door). | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Provide existing emergency lights and bell to work. | 6/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide existing battery backup lowering unit to work. | 6/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Bottom floor hoist way door missing roller, provide. | 11/5/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in the pit is unsealed, provide testing. | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Provide existing emergency lights and bell to work properly. | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 11/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide up to date MCP documentation. | 11/5/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all the non elevator related items from the elevator machine room. | 11/5/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | OSV is unsealed, provide testing. Record results. | 11/5/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV is unsealed, provide testing. Record results. | 4/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 4/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all the non elevator related items from the elevator machine room. | 4/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Provide existing emergency lights and bell to work properly. Re-inspection required | 4/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 4/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide up to date MCP documentation. | 4/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not work, needs repaired. Re-inspection required | 8/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the machine room needs to be clear and unobstructed. Remove materials from room adjacent to machine room sufficient for clear access | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide up to date MCP documentation. | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide up to date MCP documentation. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not work, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the machine room needs to be clear and unobstructed. Remove materials from room adjacent to machine room sufficient for clear access |