Inspection
Inspection Details
Equipment ID
19054
19054
Inspection Date
3/23/2022
3/23/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
F24 R26
F24 R26
External ID
e414ef07-1a9e-42d8-a51c-94fa7130d933
e414ef07-1a9e-42d8-a51c-94fa7130d933
Location
Wilhot Building
431 S JEFFERSON AVE, SPRINGFIELD, MO
Phone: (417) 864-5638
431 S JEFFERSON AVE, SPRINGFIELD, MO
Phone: (417) 864-5638
Owner
Attn: Miller, Matt
Miller, Matt
413 S Jefferson Ave, Springfield, MO 65806
Phone: (000) 000-0000
Miller, Matt
413 S Jefferson Ave, Springfield, MO 65806
Phone: (000) 000-0000
Billing
Attn: Blue Block Lofts
Blue Block Lofts
431 S Jefferson Ave, Suite 107, Springfield, MO 65806
Phone: (417) 501-8715
Email: tausha@turnkeyreonline.com
Blue Block Lofts
431 S Jefferson Ave, Suite 107, Springfield, MO 65806
Phone: (417) 501-8715
Email: tausha@turnkeyreonline.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Display a current state operating certificate in the machine room | 10/16/2019 |
| conversion | conversion | n/a | No | No | Repair the lights in sthe machine room | 10/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Have the fire extinguisher re-certified yours expired in 2019 | 8/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the expired fire extinguisher re-certified. | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as there is not enough voltage to carry the signal out. | 6/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Replace the burnt out light fixture in the machine room. | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as the incoming line does not have enough voltage. | 1/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the fire extinguisher re-certified. | 1/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the fire extinguisher re-certified | 3/31/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as it will not dial out | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove the stored lumber from the machine room. | 3/31/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 4/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as it will not dial out. | 4/4/2026 |