Inspection
Inspection Details
Equipment ID
17347
17347
Inspection Date
3/11/2022
3/11/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
6e1bbf6d-8c8b-43d4-a9ee-2f4376095703
6e1bbf6d-8c8b-43d4-a9ee-2f4376095703
Location
Sullivan Place Apartments West
3014 N 25th St, St. Louis, MO
Phone: (314) 269-8000
3014 N 25th St, St. Louis, MO
Phone: (314) 269-8000
Owner
Attn: Sullivan Place Apartments
Cohen Esrey
6800 W 64th St, Ste 101, Overland Park, KS 66202
Phone: (000) 000-0000
Cohen Esrey
6800 W 64th St, Ste 101, Overland Park, KS 66202
Phone: (000) 000-0000
Billing
Attn: Ashley Gould
Sullivan Place Apartments
3015 N 23rd St, St. Louis, MO 63107
Phone: (314) 932-5006
Email: Ashley.Gould@LiveWellCE.com
Sullivan Place Apartments
3015 N 23rd St, St. Louis, MO 63107
Phone: (314) 932-5006
Email: Ashley.Gould@LiveWellCE.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Existing cab emergency telephone does not work, and shall be repaired and tested. | 2/14/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 7/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/2/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 5/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/27/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve within 90 days. | 5/22/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 7/27/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Elevators that are equipped to operate on emergency power (noted on unit as having EP) shall be tested with no load in the car, operating on emergency power, annually. | 2/7/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 2/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/16/2026 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall be not be stored in the machine room (fan, water hose, paint, etc). | 2/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/16/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency power operation shall be tested. | 2/16/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two way communication device is not functioning properly and needs repair. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating certificate shall be displayed in the machine room in a non-combustible frame. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current ABC fire extinguisher shall be provided in machine room. | |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 204.2(a) Material for Car Enclosure Linings, and floor Coverings. | Yes | No | Replace missing and broken up floor tiles in the car as they present a trip hazard. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 207.8 | Yes | No | Emergency power operation could not be tested. |