|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair loss of phone signal.
|
1/14/2019
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
3/16/2022
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/16/2022
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
3/16/2022
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone.
|
11/13/2024
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The in-car emergency lights shall be operational.
|
11/13/2024
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in-car alarm bell shall be operational.
|
11/13/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The top floor entrance has been permanently walled off and has been taken out of service. It shall remain out of service until the following can be completed: The top floor car and hall call must be removed, the top landing door shall be bolted shut, the stop ring shall be adjusted to maintain a maximum of 24" up runby at the second landing which is now the top landing, and the hoistway limit switches shall be moved to make the second landing the top landing. Note: This elevator was locked and tagged out by TKE before we arrived today, and was put into the same condition when the inspection was completed.
|
11/13/2024
|
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
1200.6
|
x
|
|
An individual data plate shall be provided and maintained for each unit. The data plate shall indicate the code in effect at the time of any alteration and indicate the applicable requirements of Section 8.7 (8.7.3.22.1).
|
11/13/2024
|