Inspection
Inspection Details
Equipment ID
14945
14945
Inspection Date
3/8/2022
3/8/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
5508d3e5-5539-44e3-b50d-74edcbe2c2cb
5508d3e5-5539-44e3-b50d-74edcbe2c2cb
Location
Westfield Shoppingtown-South County
18 S County Center Way, St. Louis, MO
Phone: (314) 892-5203
18 S County Center Way, St. Louis, MO
Phone: (314) 892-5203
Owner
Attn: CBL & Associates Properties Inc
CBL & Associates Properties Inc
PO Box 209218, Austin, TX 78720
Phone: (423) 490-8843
Email: michael.hagen@cblproperties.com
CBL & Associates Properties Inc
PO Box 209218, Austin, TX 78720
Phone: (423) 490-8843
Email: michael.hagen@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a written maintenance control program on site including documents listed in section 8.6.1.2.2 | 10/1/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Overspeed valve is not sealed and must have a category 5 test performed within 90 days or less | 10/5/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Cab floor very worn. Repair/replace as needed. | 10/1/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Not working correctly. | 3/8/2022 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Back cab wall damaged, repair as needed. | 10/1/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Cab back wall missing hand rail, replace. | 10/1/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Expired. | 10/1/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Cab floor very worn, repair/replace as needed | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor cable is broken, needs repaired. Re-inspection required | 8/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car was not answered when tested. Provide for phone to be answered 24/7 by personnel authorized to take appropriate actions. Re-inspection required | 8/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor cable is broken, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car was not answered when tested. Provide for phone to be answered 24/7 by personnel authorized to take appropriate actions. Re-inspection required | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Failed Cat 5 inspection, completed the annual portion only. Re-inspection required |