Inspection
Inspection Details
Equipment ID
16144
16144
Inspection Date
7/31/2018
7/31/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
14
14
Governor Rope Pull
110/1200
110/1200
Door Closing Force
25/21
25/21
External ID
85cb3405-a8a5-43c1-a8e7-753d6a7562f2
85cb3405-a8a5-43c1-a8e7-753d6a7562f2
Location
The Roberts Tower
411 N 8TH ST, SAINT LOUIS, MO
411 N 8TH ST, SAINT LOUIS, MO
Owner
STL Tower Partners, LLC
357 W CHICAGO AVE STE 300, CHICAGO, IL 60654-7587
357 W CHICAGO AVE STE 300, CHICAGO, IL 60654-7587
Billing
Attn: STL Tower Partners, LLC
357 W CHICAGO AVE STE 300, CHICAGO, IL 60654-7587
357 W CHICAGO AVE STE 300, CHICAGO, IL 60654-7587
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.22 - Motor generator | 2.26.9.7 | No | No | Repair buffer switch. Reinspection required. | 7/31/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The elevator machine room cannot be used for storage. Remove the inoperable HVAC units being stored in the machine room to provide proper room for maintenance to be performed. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The 14th floor hoistway door has bent pick up roller which is required for the car door clutch to work properly. Repair or replace the bent pick up roller. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | The “Fireman’s Service Phase I” signage is not located at the primary landing adjacent to the Fireman’s Service Phase I key switch as required. Reinstall signage to comply with ASME A17.1 2004. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | The pictograph signage for “In Case of Fire” is missing at multiple elevator landings. Reinstall signage that conforms to the ASME A17.1 2004a that this elevator was designed to conform to. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The “smoke guard” barrier device, that was installed on a number of hoistway door landings, has been activated and not reset properly. The device has been temporarily held up by a piece of PVC piping rendering it inoperable in case of an actual emergency. Repair and reset all “smoke guard” barrier devices to operate as designed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Yes | No | Remove broken air conditioner from the elevator machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | Yes | No | Post Phase I instructions. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Yes | No | Numerous floors missing lobby warning placards. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Each Lobby has Ceiling drop down smoke screens are not working/disabled. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Each lobby has a Ceiling drop down smoke screens and are not working/disabled. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean car top. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Second car top light not working (no bulb). | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. |