Inspection
Inspection Details
Equipment ID
18399
18399
Inspection Date
8/10/2018
8/10/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
11
11
Governor Rope Pull
120/580
120/580
Door Closing Force
26
26
External ID
23aa4244-f775-450b-9948-359139e5f8a2
23aa4244-f775-450b-9948-359139e5f8a2
Location
Ely Walker Lofts
1520 WASHINGTON AVE, SAINT LOUIS, MO
1520 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Rafco Properties & Development
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
Billing
Attn: Rafco Properties & Development
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone inoperative. Repair | 8/28/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Door open button inoperative on Phase 11 recall. Phase II hold inoperative. Repair. 211.3 Elevator NOT red-tagged. Reinspect. | 8/28/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone inoperative. Technician measured full voltage signal on incoming line. | 7/28/2020 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 205.15 | Yes | No | Governor measured a "type C" sheave condition. Repair governor within a 6-mth time period from test date. | 7/28/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit. | 5/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency cab phone. | 7/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | The governor pull-through force is excessive. The pull-through force was over 700 lbs. repair or replacement of governor is required. If the governor is replaced, an alteration permit is required along with a reinspection. The governor rope may need to be replaced as well. | 8/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, fireman’s service, emergency systems,and buffers compressed before the inspection is completed. | 8/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet. | 8/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.1 | No | No | The emergency rescue battery in the controller shall be changed. The Manufacture’s written procedure is for replacement every 3 years. If the battery becomes depleted the elevator will automatically stop operating. Replace the battery of this elevator before it shuts down due to battery being depleted. | 8/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car is unreadable and shall be replaced.. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet. | 8/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.1 | No | No | The emergency rescue battery in the controller shall be changed. The Manufacture’s written procedure is for replacement every 3 years. If the battery becomes depleted the elevator will automatically stop operating. Replace the battery of this elevator before it shuts down due to battery being depleted. | 8/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 8/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car is unreadable and shall be replaced.. | 8/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/15/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 9/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace missing direction arrows in car door jamb | 9/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room needs to be hung on wall to meet fire code | 9/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace illegible bezels for car operating panel buttons: Car cancel and phone | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for elevator controller | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Standing water in pit. Pit shall be kept clean and dry and sump shall be repaired. |