Inspection
Inspection Details
Equipment ID
16755
16755
Inspection Date
8/6/2018
8/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
068f9c07-e098-4e26-b73b-bae082aa49b1
068f9c07-e098-4e26-b73b-bae082aa49b1
Location
Convention Center
600 N 6TH ST, SAINT LOUIS, MO
600 N 6TH ST, SAINT LOUIS, MO
Owner
Metro Accounts Payable
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
Billing
Attn: Metro Accounts Payable
PO BOX 1349, SAINT LOUIS, MO 63188-1349
PO BOX 1349, SAINT LOUIS, MO 63188-1349
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | No | Yes | Failed brake torque test. Red tagged unit. | 8/5/2019 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | Need to replace handrail guides on both sides at top of escalator. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | Replace handrail guides on both sides at top of escalator. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.8 - Deck barricades and antislide devices | 8.6.8.11 | No | No | Anti slide device missing center | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.19 - Maintenance records | 8.6.1.4 | No | No | Need maintenance control program on site posted on controller | |
| A17.1-2016 : Elevators | 7.15 - Balustrades | 8.11.4.1(o) | No | No | Screws holding bulstrade molding have to be flushed | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.14 | No | No | Machine space cover switch not working | |
| A17.1-2016 : Elevators | 7.15 - Balustrades | 8.11.4.1(o) | No | No | Balustrade panels must be flushed | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.6 - Caution Signs | 6.1.6.9 | No | No | Caution signage bottom left needs replacing | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(F) | No | No | Many balustrade panels need to be aligned correctly | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Need to perform step indexing test. Re-inspection required |