Inspection
Inspection Details
Equipment ID
18701
18701
Inspection Date
3/21/2022
3/21/2022
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
990
990
Slide
Governor Rope Pull
Door Closing Force
External ID
fb73ee3c-6869-458f-9f2e-68d5aef20245
fb73ee3c-6869-458f-9f2e-68d5aef20245
Location
Trinity Park Apartment
11019 MOLLERUS DR, SAINT LOUIS, MO
Phone: (314) 868-4300
11019 MOLLERUS DR, SAINT LOUIS, MO
Phone: (314) 868-4300
Owner
Attn: Nicole Hammett
Sansone Group
120 S Central Ave, Ste 500, St. Louis, MO 63105
Phone: (314) 336-2345
Email: nhammett@sansonegroup.com
Sansone Group
120 S Central Ave, Ste 500, St. Louis, MO 63105
Phone: (314) 336-2345
Email: nhammett@sansonegroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The machine room door shall be self-closing and self-locking. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting shall work. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room shall be cleaned of dirt and debris. | 10/25/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | A rope data tag is required on the hoist ropes. | 10/25/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall work. | 10/25/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | A fire service testing log shall be kept on-site. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A maintenance log shall be kept on-site. | 10/25/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | The hoist ropes are rouging and have crown breaks and require replacement. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.34 - Flexible Hydraulic Hose and Fitting Assemblies | 1004.2(b)(17) | No | No | The high pressure hose is expired. If the unit is equipped with a rupture valve the hose does not need replacing, if no rupture valve is present the high pressure hose shall be replaced. | 2/22/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/8/2020 |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 1001.2(a)(2) | No | No | The in car stop switch does not stop the elevator. Repair or replace the switch for proper operation. | 2/24/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/23/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed. Perform test, tag, and seal upon completion. | 7/27/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/11/2023 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Top of hoistway light shall be operational. | 7/11/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Hydraulic pipe in pit is rusted. Take corrective action as needed. |