Inspection
Inspection Details
Equipment ID
7094
7094
Inspection Date
2/23/2022
2/23/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
f23b0da4-3f8f-4ae4-8e71-3f702e408f59
f23b0da4-3f8f-4ae4-8e71-3f702e408f59
Location
Powell Gardens
1609 NW US Hwy 50, Kingsville, MO
Phone: (816) 697-2600
1609 NW US Hwy 50, Kingsville, MO
Phone: (816) 697-2600
Owner
Attn: Powell Gardens
Powell Gardens
1609 NW US Hwy 50, Kingsville, MO 64061
Phone: (816) 697-2600
Email: accounting@powellgardens.org
Powell Gardens
1609 NW US Hwy 50, Kingsville, MO 64061
Phone: (816) 697-2600
Email: accounting@powellgardens.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | door reversal light ray is not working, repair or replace with working light ray door reversal device | 7/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post a log in the machine room | 7/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | replace broken alarm bell chicklet in the car operating panel | 7/22/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit light is burnt out, replace bulb | 3/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean pit, oil on pit floor | 3/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | state operating certificate in the machine room is to be updated every year, the one in the machine room is from 2017 | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | the monthly fire service test log in not being filled out monthly | 3/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out monthly | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher last inspection was in 2020, it is to be inspected annually | 3/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate is to be displayed in the machine room, the most current certificate expired in 2021 | 3/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | The monthly fire service test log is not being filled out, post a monthly fire service test log in the machine room and fill it out log monthly | 3/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is burnt out, replace bulb | 3/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Only has one working light bulb in the elevator cab ceiling, required to have at least two working light bulbs in the elevator cab ceiling | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not have a dial tone | 4/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate is to be displayed in the machine room, the most current certificate expired in 2021 | 3/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | The monthly fire service test log is not being filled out since 2020, post a monthly fire service test log in the machine room and fill it out log monthly | 3/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is burnt out, replace bulb or repair the circuit so the light works | 3/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Only has one working light bulb in the elevator cab ceiling, required to have at least two working light bulbs in the elevator cab ceiling | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not have a dial tone, provide working phone line to the elevator controller | 7/16/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate is to be displayed in the machine room, the most current certificate expired in 2021 | 3/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Do not store non elevator related items in the machine room | 3/27/2026 |