Inspection
Inspection Details
Equipment ID
10420
10420
Inspection Date
8/15/2018
8/15/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
27
27
External ID
86b0d75d-8d3d-4b64-abd7-fa6d7f7eed18
86b0d75d-8d3d-4b64-abd7-fa6d7f7eed18
Location
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO
10010 KENNERLY RD, SAINT LOUIS, MO
Owner
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Billing
Attn: St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The emergency car lighting could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. | 10/20/2020 |
| conversion | conversion | n/a | No | No | The emergency alarm bell could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. | 10/20/2020 |
| conversion | conversion | n/a | No | No | The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The emergency car lighting could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation.. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The emergency alarm bell could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 8.6.4.15 Car Emergency Systems - The emergency car lighting is not operational, likely indicating that the light bulbs need replacement. The fixture shall be repaired to operate. | 8/13/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II operation, the elevator car will not override the security feature on the car operating panel. Security shall be overridden in fireman’s service. | 8/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 8/10/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel. | 7/16/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator and fire service testing shall be done. Scheduled 8/19/25 | 8/19/2025 |