Inspection
Inspection Details
Equipment ID
10422
10422
Inspection Date
8/15/2018
8/15/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
29
29
External ID
4bc88a41-a602-418f-85f8-801cfc053101
4bc88a41-a602-418f-85f8-801cfc053101
Location
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO
10010 KENNERLY RD, SAINT LOUIS, MO
Owner
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Billing
Attn: St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. | 7/18/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit shall be cleaned of dust and debris. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. | 7/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. | 8/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 8/10/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The hoistway door at the 7th landing is not self-closing/self-locking. The hoistway door shall be adjusted. | 3/24/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel. | 11/22/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 3/24/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | The electrical ductwork at the top of the hoistway is missing the top portions cover. Install a duct cover. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator testing and fire service shall be tested. Scheduled 8/19/25 | 8/19/2025 |