Inspection
Inspection Details
Equipment ID
8226
8226
Inspection Date
8/22/2018
8/22/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
6a01669a-baf6-402e-ab35-841c59886b78
6a01669a-baf6-402e-ab35-841c59886b78
Location
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO
10010 KENNERLY RD, SAINT LOUIS, MO
Owner
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Billing
Attn: St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | There is no fireman?s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be repaired to properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/12/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 8/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator testing and fire service shall be tested. Scheduled on 8/19/25 | 8/19/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 7/14/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 7/14/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. This is the 3rd consecutive year that this violation has been issued. Corrections SHALL be made in 30 days or the elevator will be removed from service due to not having a current certificate of compliance. Reinspection is required for compliance. |