Inspection
Inspection Details
Equipment ID
10501
10501
Inspection Date
4/5/2022
4/5/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
f0dd1a7d-05e7-4c0c-bca1-1a27497e2289
f0dd1a7d-05e7-4c0c-bca1-1a27497e2289
Location
Lamplighter Inn North
2820 N GLENSTONE AVE, SPRINGFIELD, MO
Phone: (417) 830-6297
2820 N GLENSTONE AVE, SPRINGFIELD, MO
Phone: (417) 830-6297
Owner
Attn: Phil Gnau
Lamplighter Inn North
2820 N Glenstone Ave, Springfield, MO 65803
Phone: (000) 000-0000
Lamplighter Inn North
2820 N Glenstone Ave, Springfield, MO 65803
Phone: (000) 000-0000
Billing
Attn: Lamplighter Inn North
Elliott Lodging
1736 E Sunshine, Springfield, MO 65804
Phone: (417) 830-6297
Email: phil@elliottlodging.com
Elliott Lodging
1736 E Sunshine, Springfield, MO 65804
Phone: (417) 830-6297
Email: phil@elliottlodging.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Povide a light switch in the pit accessable to the lowest landing door. | 7/31/2018 |
| conversion | conversion | n/a | No | No | Enclose the elevator equipment with a 6 foot high chain link fence with a self closing self latching gate with a lock always locked outside never locked inside. maintain a minimum of 36 inches clear working splace around the equipment. | 7/31/2018 |
| conversion | conversion | n/a | No | No | Provide a capacity plate in the car. stating 2000 lb. capacity. | 7/31/2018 |
| conversion | conversion | n/a | No | No | Clean the machine spaace of combustibles, ie leaves, wood etc. anso the pit is very dirty and needs cleaned | 7/31/2018 |
| conversion | conversion | n/a | No | No | Replace the burnt out lights in the machine room | 7/31/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. This was on last years inspection too. | 5/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Provide a chainlink fence seperating the machine room from the other equipment serving the building not pretaining to the operation of the elevator | 5/21/2020 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.11.3.1.2(h) | No | No | Pump unit oil pan required to be pumped out | 2/14/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | No Records | 2/14/2022 |
| A17.1-2016 : Elevators | 2.9 - Guarding of exposed auxiliary equipment | 8.11.3.1.2(l) | No | No | Install proper cover for pump & motor | 2/14/2022 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | No | No | Jack seal needs to be replaced | 2/14/2022 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Cab lighting circuit being used to supply power door reopen device (NEC 620.22) | 4/5/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Alarm operable. 1.6 | 6/5/2024 |