Inspection
Inspection Details
Equipment ID
8017
8017
Inspection Date
9/14/2017
9/14/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Kiel Center (Savvis Center)
1401 Clark Ave, St. Louis, MO
Phone: (314) 589-5982
1401 Clark Ave, St. Louis, MO
Phone: (314) 589-5982
Owner
Scottrade Center
1401 Clark Ave, St Louis, MO 63103
1401 Clark Ave, St Louis, MO 63103
Billing
Attn: Scottrade Center
1401 Clark Ave, , MO 63103
1401 Clark Ave, , MO 63103
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace broken step tread | 11/18/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(E) | No | No | Replace broken comb plates where needed. | 11/18/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(E) | No | No | Replace broken step treads where needed. | 11/18/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(G) | No | No | Perform step/skirt index when construction is finished. | 11/18/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(F) | No | No | Need to straighten lower deck plate. | 11/18/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Upper demarcation light no working | 12/7/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean pits | 11/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Upper and lower walk-on deck switches are taped/defeated. Repair/adjust. | 12/17/2024 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. Note: Certificate expired 7/1/2018. | 11/18/2025 |
| A17.1-2016 : Elevators | 7.1 - General fire protection | 6.1.1 | Yes | No | Enclose the upper escalator pit. There is a wide panel of the enclosure missing at the rear of the pit which opens into a utility closet. |