Inspection
Inspection Details
Equipment ID
1449
1449
Inspection Date
4/12/2022
4/12/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
a54866c5-bdfa-4071-b994-5721fc6d565c
a54866c5-bdfa-4071-b994-5721fc6d565c
Location
Macy's Midwest
1 Mid Rivers Mall, St. Peters, MO
Phone: (636) 278-6660
1 Mid Rivers Mall, St. Peters, MO
Phone: (636) 278-6660
Owner
Attn: Cathie Sherman
MACY'S MSOC VERTICAL COMPLIANCE
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (732) 734-3438
Email: Cathie.Sherman@macys.com
MACY'S MSOC VERTICAL COMPLIANCE
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (732) 734-3438
Email: Cathie.Sherman@macys.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State certificate in machine | 10/19/2018 |
| conversion | conversion | n/a | No | No | Repair skirt lighting | 10/19/2018 |
| conversion | conversion | n/a | No | No | Post current State Certificate in machine room | 10/19/2018 |
| conversion | conversion | n/a | No | No | Repair skirt lighting | 10/19/2018 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Need code compliant signage at entrance and egress of unit | 11/26/2019 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current State certificate in machine room | 12/1/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Repair comb lighting | 12/1/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(D) | No | No | Replace step chains | 12/1/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair skirt lights at entrance | 4/12/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.11.4.1(e) Lighting (demarcation and step lighting) | No | No | Repair skirt lighting at entrances | 11/12/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair Skirt Lighting Top and Bottom Entrances. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean Down Truss. | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post Current Certificate. |